Test probe-type low water cutoff
What is going on
Checks that the probe-type low water cutoff stops firing at low water and allows firing once refilled.
Check in this order
- Turn off power to the boiler and wait 5 minutes.
- Drain water to the bottom of the gauge glass.
- Turn on power.
- Set the thermostat to call for heat. The red neon lamp on the lower water cutoff should light.
- Wait 5 minutes. The boiler should not fire.
- Refill the boiler to the correct waterline. The red lamp should go off.
- Wait 5 minutes. The boiler should fire.
- Return the thermostat to its normal setting.
Applies to: EG and PEG steam boilers with probe-type LWCO
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 70. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.