CSD-1 fixed high limit field test (simulation #2)

Vitodens 200-W B2HB

What is going on

Alternate CSD-1 high limit test using the relays test and a throttled boiler valve.

Check in this order

  1. Throttle the boiler valve so the burner runs with as little flow as possible.
  2. Run the boiler to high fire using the relays test.
  3. When the burner shuts down on the electronic limit, close the ball valve to stop the flow.
  4. Confirm the boiler temperature keeps rising until the fixed high limit trips.
  5. Once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down safely.

Applies to: Vitodens 200-W B2HB, all models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.