CSD-1 fixed high limit field test (simulation #2)
What is going on
Alternate CSD-1 high limit test using the relays test and a throttled boiler valve.
Check in this order
- Throttle the boiler valve so the burner runs with as little flow as possible.
- Run the boiler to high fire using the relays test.
- When the burner shuts down on the electronic limit, close the ball valve to stop the flow.
- Confirm the boiler temperature keeps rising until the fixed high limit trips.
- Once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down safely.
Applies to: Vitodens 200-W B2HB, all models
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.