Circulation pump connection
What is going on
Pumps can be hard-wired to the Power Pump Module terminal strip, or Viessmann pre-wired pumps can be plugged into the Rast-5 terminals. Only Viessmann pre-wired pumps may be used with the plug-in terminals.
Check in this order
- Use only Viessmann pre-wired (plug-in) circulating pumps if the plug-in terminals are used.
- Insert the supplied strain relief through the Power Pump Module knock-out and fasten it with the nut.
- Connect the Rast-5 connector to the matching plug-in terminal on the Power Pump Module.
- If pre-wired pumps are used, do not also connect a pump to the matching hard-wired terminal.
- For underfloor heating, also install an adjustable high limit. Put the fixed high limit in the heating supply pipe after the mixing valve and the heating circuit pump.
Applies to: Boiler circuit pump, DHW production pump, DHW recirculation pump, Vitotronic 300
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 installation instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.