Navien · Boiler troubleshooting
Wiring zone pumps with domestic hot water (DHW) recirculation
What is going on
The NCB700 can run 3 zone pumps and DHW recirculation together. Recirculation can be set to a timer, aquastat or HotButton input, or the boiler can control it through the DHW Recirculation menu.
Check in this order
- Wire the zone pumps and thermostats as in the zone pump diagram.
- Connect the recirculation pump (max 2.5 A) to its terminal with line and neutral.
- Connect the recirculation timer, aquastat or HotButton push button if the Recirculation menu is set to External Recirculation.
- If the DHW Recirculation menu is set to Always On, Intelligent or Weekly, no extra aquastat or HotButton is needed.
- If using Mixed Preheat, no recirculation pump is needed; select Mixed Preheat in the DHW Recirculation menu.
- If using External Recirculation, install a recirculation pump and select External Recirculation in the DHW Recirculation menu.
Applies to: NCB700 boilers with zone pumps and DHW recirculation
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 211. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.