Viessmann · Boiler troubleshooting
Check and service the neutralisation unit (if fitted)
What is going on
Applies when a neutralisation unit accessory is installed. The granulate is used up as it neutralises the condensate.
Likely causes
- Condensate pH below 6.5
- Contaminated neutralisation unit
Check in this order
- Check the condensate pH with a pH test strip (field supplied). If pH is below 6.5, replace the granulate.
- If contaminated, rinse the unit with tap water.
- Add granulate up to the mark on the cartridge. Do not fill below the red minimum filling level marking.
Applies to: Vitodens 100-W, WB1B with neutralisation unit
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 70. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.