Viessmann · Boiler troubleshooting

Check and service the neutralisation unit (if fitted)

Vitodens 100-W, WB1B

What is going on

Applies when a neutralisation unit accessory is installed. The granulate is used up as it neutralises the condensate.

Likely causes

  • Condensate pH below 6.5
  • Contaminated neutralisation unit

Check in this order

  1. Check the condensate pH with a pH test strip (field supplied). If pH is below 6.5, replace the granulate.
  2. If contaminated, rinse the unit with tap water.
  3. Add granulate up to the mark on the cartridge. Do not fill below the red minimum filling level marking.

Applies to: Vitodens 100-W, WB1B with neutralisation unit

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 70. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.