Navien · Boiler troubleshooting

Set up Wi-Fi client connection

Modbus/BACnet Gateway

What is going on

Connect the gateway to a local wireless access point as a Wi-Fi client.

Check in this order

  1. On the FS-GUI Network Settings page, open the Wi-Fi Client tab.
  2. Set Wi-Fi Status to ENABLED.
  3. Enter the Wi-Fi SSID and Wi-Fi Password for the local access point.
  4. Enable DHCP for automatic settings, or fill in IP Address, Network and related fields manually.
  5. If connected to a router, set the IP gateway to the router's IP address.
  6. Click Update Wi-Fi Settings, then click System Restart.
  7. Go to Common settings and set Primary Connection to Wi-Fi Client.

Applies to: Gateway Wi-Fi client mode

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Modbus/BACnet Gateway Start-up Guide, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.