Test and analysis equipment

Vitorond 200 VD2

What is going on

Use only calibrated equipment.

Check in this order

  1. Flue gas analyzer to measure % CO2 or O2.
  2. Multimeter for 0-120 VAC, 0-12 AAC and 0-20 microamps DC.
  3. Smoke test gun.
  4. Oil pump pressure gauge and oil pump vacuum gauge.
  5. Gas pressure gauge for 0-7 in. w.c. (accurate) and up to 28 in. w.c., or a non-electric Magnehelic gauge.
  6. Carbon monoxide meter, 0-400 ppm.
  7. Efficiency calculator or tables.
  8. Stack thermometer, 0 to 500 F (0 to 260 C).
  9. 1/8 in. NPT male to 1/4 in. barb adaptor and tubing for pressure measurement.

Applies to: Vitorond 200 VD2 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.