Weil-McLain · Boiler troubleshooting

No display and no boiler components operating

SVF 500/600 Series 1

What is going on

Control is not receiving 120 V power.

Likely causes

  • Service switch or circuit breaker off
  • No 120 Vac supply at service switch
  • Blown 4 A line voltage fuse

Check in this order

  1. Turn on the service switch or reset the circuit breaker.
  2. Check for 120 Vac at the service switch. If absent, correct the supply.
  3. Check for 120 Vac at the line voltage terminal block J1 on the circuit board.
  4. Inspect the 4 A fuse and replace if necessary.
  5. If the fuse blows again, recheck wiring per diagrams.

Applies to: SVF 500/600 Series 1

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 Boiler Manual, p. 124. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.