Weil-McLain · Boiler troubleshooting
No display and no boiler components operating
What is going on
Control is not receiving 120 V power.
Likely causes
- Service switch or circuit breaker off
- No 120 Vac supply at service switch
- Blown 4 A line voltage fuse
Check in this order
- Turn on the service switch or reset the circuit breaker.
- Check for 120 Vac at the service switch. If absent, correct the supply.
- Check for 120 Vac at the line voltage terminal block J1 on the circuit board.
- Inspect the 4 A fuse and replace if necessary.
- If the fuse blows again, recheck wiring per diagrams.
Applies to: SVF 500/600 Series 1
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 Boiler Manual, p. 124. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.