Venting requirements (Category IV, positive pressure)

NCB700

What is going on

The boiler is a Category IV appliance and needs a special vent system. The vent operates under positive pressure. Improper venting can cause high carbon monoxide levels and serious injury or death. Vent systems must be installed only by licensed professionals.

Check in this order

  1. Vent the exhaust gases directly outdoors using the approved vent materials and follow the venting instructions.
  2. Do not connect vents from naturally drafted gas appliances to any part of a mechanical positive-pressure vent system.
  3. Install the vent per the National Fuel Gas Code (ANSI Z223.1/NFPA 54) or CAN/CGA B149.1, and all local codes.
  4. Keep the vent system as short and straight as possible.
  5. Install the boiler as close as possible to the vent termination.
  6. Do not connect the boiler vent to the vent of another gas appliance or to a chimney.
  7. Slope horizontal vent runs upward toward the termination at 1/4 in per ft (2% slope).
  8. Seal every joint in the intake and exhaust vent, from the boiler connection to the termination, so it is gas-tight.
  9. Do not insulate non-metallic vent materials.
  10. Keep the intake and exhaust vent terminations clear of snow, ice and other obstructions. The building owner is responsible for this and for periodic maintenance.

Applies to: NCB700 venting

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation & operation manual, pp. 231-232. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.