Probe type low water cutoff: clean and test

CGa Series 4CGi Series 5EG Series 7PEG Series 7LGB Series 2 & 3

What is going on

Periodic cleaning and function test of a probe type low water cutoff.

Check in this order

  1. Turn off power to the boiler and wait 5 minutes.
  2. Drain water down to the bottom of the gauge glass.
  3. Turn power back on.
  4. Set the thermostat to call for heat; the red neon lamp on the low water cutoff should light.
  5. Wait 5 minutes; the boiler should not fire.
  6. Refill to the correct waterline; the red lamp should go off.
  7. Wait 5 minutes; the boiler should fire.
  8. Return the thermostat to its normal setting.

Applies to: Probe type low water cutoff

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.