Weil-McLain · Boiler troubleshooting
Annual startup: check boiler relief valve
What is going on
Operate the relief valve lever to confirm the waterway is clear. Relief valve reinspection is also required on a set schedule.
Likely causes
- Mineral deposits blocking the valve
- Valve weeping or not seating
- System overpressure from a waterlogged or undersized expansion tank
Check in this order
- Before lifting the lever, confirm a discharge line is piped to a safe disposal point.
- Lift the lever and confirm water flows.
- If the valve weeps or will not seat, replace it.
- Before replacing, confirm the weeping is from the valve and not from system overpressure due to expansion tank waterlogging or undersizing.
- If no water flows when the lever is lifted, the valve is inoperative. Shut the boiler down until a new relief valve is installed.
- Operate the lever at least once a year.
- Have a licensed plumbing contractor or authorized inspection agency reinspect the relief valve at least every three years.
Applies to: SlimFit 1000-2000 MBH Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 89. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.