Weil-McLain · Boiler troubleshooting

Annual startup: check boiler relief valve

SlimFit Series 2

What is going on

Operate the relief valve lever to confirm the waterway is clear. Relief valve reinspection is also required on a set schedule.

Likely causes

  • Mineral deposits blocking the valve
  • Valve weeping or not seating
  • System overpressure from a waterlogged or undersized expansion tank

Check in this order

  1. Before lifting the lever, confirm a discharge line is piped to a safe disposal point.
  2. Lift the lever and confirm water flows.
  3. If the valve weeps or will not seat, replace it.
  4. Before replacing, confirm the weeping is from the valve and not from system overpressure due to expansion tank waterlogging or undersizing.
  5. If no water flows when the lever is lifted, the valve is inoperative. Shut the boiler down until a new relief valve is installed.
  6. Operate the lever at least once a year.
  7. Have a licensed plumbing contractor or authorized inspection agency reinspect the relief valve at least every three years.

Applies to: SlimFit 1000-2000 MBH Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 89. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.