Viessmann · Boiler troubleshooting

Space heating: how the boiler water setpoint and modulation are set

Vitodens 200-W B2HB

What is going on

The control unit sets a boiler water setpoint from outdoor temperature (or room temperature if a room-dependent remote control is connected) and the heating curve slope and shift. The burner control unit sets modulation from that setpoint and actual boiler water temperature. The electronic limit is 180°F (82°C) boiler water. The fixed high limit in the safety chain locks out the burner at 210°F (99°C). With zone circuit operation, the boiler runs only when a room thermostat (dry contact) calls for heat.

Check in this order

  1. Confirm the outdoor sensor or room-dependent remote control is connected so the setpoint can be calculated.
  2. Check the heating curve slope and shift against the system type.
  3. Check the boiler water setpoint against the actual temperature to confirm modulation.
  4. For zone operation, confirm the room thermostat dry contact closes before expecting the boiler to run.

Applies to: Vitodens 200-W B2HB space heating

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 33. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.