Viessmann · Boiler troubleshooting
Check power pump module fuse F1
What is going on
Check the fuse on the power pump module.
Check in this order
- Switch off the main power supply. The boiler ON/OFF switch does not disconnect power to the power pump module, so the main service switch or breaker must be turned off.
- Flip down and remove the control unit.
- Remove the power pump module cover plate.
- Check fuse F1, T6.3A slow blow.
- Replacement fuses come from Viessmann in packs of 10 (Part No. 7815 580).
Applies to: Power pump module fuse F1 T6.3A
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 81. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.