Viessmann · Boiler troubleshooting

Check power pump module fuse F1

Vitodens 100-WWB1B

What is going on

Check the fuse on the power pump module.

Check in this order

  1. Switch off the main power supply. The boiler ON/OFF switch does not disconnect power to the power pump module, so the main service switch or breaker must be turned off.
  2. Flip down and remove the control unit.
  3. Remove the power pump module cover plate.
  4. Check fuse F1, T6.3A slow blow.
  5. Replacement fuses come from Viessmann in packs of 10 (Part No. 7815 580).

Applies to: Power pump module fuse F1 T6.3A

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 81. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.