Viessmann · Boiler troubleshooting

Convert boiler from natural gas to liquid propane

Vitodens 200-W B2HA

What is going on

Factory set to natural gas (coding 82 = 0). Conversion uses coding level 2 and a gas valve adjustment. Fuel conversion labels must be applied.

Check in this order

  1. Set adjusting screw A at the gas valve to 2 (2.5 mm hex key).
  2. Switch ON/OFF switch 8 to ON. Slide the black control cover outward to reach it.
  3. Enter coding level 2 (see page 47).
  4. Open the General menu.
  5. Set coding address 11 to 9.
  6. Set coding address 82 to 1 (liquid propane gas).
  7. Return to coding address 11 and select any value except 9.
  8. End coding level 2 and open the gas shut-off valve.
  9. Apply the supplied fuel conversion labels.

Applies to: Vitodens 200-W B2HA 45, 60

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.