Viessmann · Boiler troubleshooting

Replacing a boiler water temperature sensor

Vitocrossal 300 CA3B

What is going on

There is one boiler water temperature sensor on each boiler section.

Check in this order

  1. Remove the spring clip from the sensor well and set it aside.
  2. Remove the boiler water temperature sensor from the sensor well.
  3. Disconnect the sensor cable plugs for that section.
  4. Connect the new sensor to the cable plugs and install it in the sensor well.
  5. Reinstall the spring clip.

Applies to: Vitocrossal 300 CA3B 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.