Connect NFB-301C/399C boiler to gateway R1 port

Modbus/BACnet Gateway

What is going on

Wire the boiler's front-panel 3-pin terminal block to the gateway R1 Phoenix connector. Keep R1 Switch 4 OFF and bond RS-485 GND per standard practice.

Check in this order

  1. Set R1 DIP Switch 4 to OFF.
  2. Connect the gateway R1 3-pin Phoenix connector to the boiler's 3-pin terminal block on the right side of the front panel.
  3. Wire A to TX+ / RS-485+, B to RX- / RS-485-, and G to RS-485 GND.
  4. Use standard grounding principles for the RS-485 GND connection.

Applies to: NFB-301C/399C boiler to gateway R1

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien Modbus/BACnet gateway installation and operation manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.