Navien · Boiler troubleshooting
Connect NFB-301C/399C boiler to gateway R1 port
What is going on
Wire the boiler's front-panel 3-pin terminal block to the gateway R1 Phoenix connector. Keep R1 Switch 4 OFF and bond RS-485 GND per standard practice.
Check in this order
- Set R1 DIP Switch 4 to OFF.
- Connect the gateway R1 3-pin Phoenix connector to the boiler's 3-pin terminal block on the right side of the front panel.
- Wire A to TX+ / RS-485+, B to RX- / RS-485-, and G to RS-485 GND.
- Use standard grounding principles for the RS-485 GND connection.
Applies to: NFB-301C/399C boiler to gateway R1
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien Modbus/BACnet gateway installation and operation manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.