Hydrostatic pressure test of the boiler

Vitodens 100-W WB1B

What is going on

Pressure test the boiler before it is connected to piping or power. Hold 4 bar (60 psig) for 15 minutes and look for leaks.

Likely causes

  • Gauge reading drops below test pressure, indicating water loss through a leak

Check in this order

  1. Cap the supply and return connections (3/4 in NPT male).
  2. Connect a 1/2 in garden hose to the boiler drain valve and fill slowly until the gauge reads 4 bar (60 psig).
  3. Hold pressure for 15 minutes and do not leave the boiler unattended.
  4. Inspect all joints and safety devices with a flashlight for leaks.
  5. Repair every leak found.
  6. After 15 minutes, open the drain valve slowly to release water.
  7. Remove the caps and install the pressure relief valve in place of the 3/4 in cap.
  8. Check the fill procedure before running the boiler.

Applies to: Boiler pressure test

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W WB1B installation manual, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.