Hydrostatic pressure test of the boiler
What is going on
Pressure test the boiler before it is connected to piping or power. Hold 4 bar (60 psig) for 15 minutes and look for leaks.
Likely causes
- Gauge reading drops below test pressure, indicating water loss through a leak
Check in this order
- Cap the supply and return connections (3/4 in NPT male).
- Connect a 1/2 in garden hose to the boiler drain valve and fill slowly until the gauge reads 4 bar (60 psig).
- Hold pressure for 15 minutes and do not leave the boiler unattended.
- Inspect all joints and safety devices with a flashlight for leaks.
- Repair every leak found.
- After 15 minutes, open the drain valve slowly to release water.
- Remove the caps and install the pressure relief valve in place of the 3/4 in cap.
- Check the fill procedure before running the boiler.
Applies to: Boiler pressure test
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W WB1B installation manual, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.