Weil-McLain · Boiler troubleshooting

Check venting system operation (monthly in heating season)

EGPEG

What is going on

Check the vent system at least once a month during the heating season while the boiler is firing. A proper draft keeps the flame steady when a test flame is held near the vent.

Likely causes

  • Obstructed flue or vent
  • Exhaust fans or other equipment in the boiler room pulling air
  • Other causes of improper venting

Check in this order

  1. With the boiler firing, hold a lit candle or match just below the lower edge of the draft hood skirt.
  2. If the flame burns undisturbed, the vent system is working properly.
  3. If the flame blows out or flickers strongly, inspect the vent system for obstructions and other causes of improper venting, such as exhaust fans in the boiler room.

Applies to: EG and PEG Series 7 boilers with draft hood

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.