Viessmann · Boiler troubleshooting

Heating system design version 7: heating circuit plus low temperature circuit with Vitorond on shunt pump

Vitotronic 100 GC1Vitocontrol-S VD2/CT3/CM2

What is going on

Vitocrossal 300 CT3 as lead boiler and Vitorond 200 VD2 as lag boiler, operated by a Viessmann control system with outdoor reset, modulating boiler water temperature and load-dependent sequential control. Return temperature control for the Vitorond uses the shunt pump and closing the isolation valve. Sensor T1 controls the isolation valve. Sensor T2 switches the shunt pump. Boiler supply temperature is set automatically over LON BUS.

Check in this order

  1. Set the coding for system version 7 on every Vitotronic 100 GC1.
  2. Set the Vitocontrol-S coding as listed in the system version 7 coding table.
  3. For the low temperature boiler, connect temperature sensor T1 to plug aJA and temperature sensor T2 to plug aJB.
  4. Connect at least 15% of the rated output of the Vitocrossal 300 to the lower return connection. Provide return temperature control as an accessory or on site.
  5. Check the connection diagram on site for completeness and function.

Applies to: Heating system design version 7

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 22-24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.