Viessmann · Boiler troubleshooting
Prepare CombiPLUS connections and fittings
What is going on
Fit the extension fittings and system connection adaptors to the CombiPLUS before mounting it.
Check in this order
- Remove the four screws on the CombiPLUS A cover, then pull the cover straight out and set it aside.
- Lubricate both extension fitting O-rings with the supplied lubricant and fit them to the lower part of the extension fittings.
- Insert each extension fitting at a slight angle through the rubber grommets into the main supply/return connections, and make sure they are fully seated.
- Fit a locking clip into the lower part of each extension fitting, then pull up on each fitting to confirm it is locked.
- Fit the heating circuit gaskets into the adaptors and install the heating circuit adaptors on the system supply/return connections.
- Fit the DHW gaskets into the DHW adaptors and install them on the DHW/DCW connections. Do not overtighten the adaptor fittings.
Applies to: CombiPLUS A, all Vitodens 100-W WB1B models
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W WB1B installation and service instructions, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.