Sidewall concentric termination: location and clearances
What is going on
Pick a termination spot that keeps flue plume away from windows, plants, AC units and people, and out of wind eddies, inside corners and recessed areas. Terminate at least 6 ft from adjacent walls, at least 5 ft below a roof overhang, at least 7 ft above a public walkway, and at least 3 ft above any forced air intake within 10 ft. Keep the vent at least 12 in below or horizontally from any door, window or gravity inlet for appliances up to 150,000 BTU/hr, or 48 in for larger appliances. Keep the air inlet at least 12 in above grade or snow line. Keep the termination at least 4 ft horizontally from any electric meter, gas meter, regulator, relief valve or other equipment. Never terminate above or below these within 4 ft. Do not terminate above a door or window or under a deck.
Check in this order
- Read the surroundings and avoid wind eddies, corners, window wells and recessed areas.
- Check each clearance against the minimums in this section before cutting any wall.
- Keep the termination out of reach of stones, balls, leaves and sediment, and guard it against condensate damage to finishes.
- Confirm a bird screen is fitted at every vent and air termination, buying it separately if the kit does not include one.
Applies to: Sidewall 3 in or 4 in concentric vent/air termination
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual, p. 72-73. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.