Viessmann · Boiler troubleshooting
Check expansion tank and system pressure
What is going on
Check the diaphragm expansion tank pressure against the static water fill pressure on a cold system.
Likely causes
- Cyclical pressure swings or large pressure differences indicate a system fault.
Check in this order
- Carry out this test on a cold system.
- Drain the system or close the cap valve on the diaphragm expansion tank.
- Reduce the pressure until the gauge reads 0.
- Check that the 60 F (15.5 C) water fill pressure equals the expansion tank pressure.
- Follow the expansion tank manufacturer's instructions.
- Fix any pressure fault right away to protect the other system components.
Applies to: Diaphragm expansion tank
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.