Viessmann · Boiler troubleshooting

Check expansion tank and system pressure

Vitocrossal 200 CM2

What is going on

Check the diaphragm expansion tank pressure against the static water fill pressure on a cold system.

Likely causes

  • Cyclical pressure swings or large pressure differences indicate a system fault.

Check in this order

  1. Carry out this test on a cold system.
  2. Drain the system or close the cap valve on the diaphragm expansion tank.
  3. Reduce the pressure until the gauge reads 0.
  4. Check that the 60 F (15.5 C) water fill pressure equals the expansion tank pressure.
  5. Follow the expansion tank manufacturer's instructions.
  6. Fix any pressure fault right away to protect the other system components.

Applies to: Diaphragm expansion tank

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.