Weil-McLain · Boiler troubleshooting
Prepare and open the boiler to access the flue side
What is going on
Shut the boiler down and let it cool before opening it. Removing the gas valve is optional and only needed for extra clearance. The boiler contains ceramic fiber materials, so handle them with care. Label all wires before disconnecting them.
Check in this order
- Follow the To Turn Off Gas to Appliance instructions on the boiler and close the boiler manual gas valve.
- Allow the boiler to cool to room temperature if it has been firing.
- Unlatch both side latches on the jacket door and lift the door off.
- Move the display bracket aside and disconnect its cable carefully so it does not snag or get pulled tight.
- Remove the air silencer by releasing its clip and sliding it off the venturi.
- Label and disconnect the gas valve harness, the low voltage and high voltage blower harnesses.
- Optional loosen the U-bolt and the three gas valve bracket screws, remove the four flange screws, and unscrew the swivel nut at the venturi using two wrenches.
- Remove the two 5mm blower lock nuts with the 8mm wrench and remove the blower assembly. Inspect the blower gasket.
- On 110 and 199 models, remove the burner tube from the cover plate.
- Cut the two tapes holding the top cover plate insulation and set the insulation aside.
- Disconnect the ground wire and the ignition cable from the ignition electrode.
- Remove the two 3mm Allen igniter bolts and the ignition electrode. Discard the used gasket.
- Inspect the igniter ceramic and electrodes. Clean the electrodes with steel wool. Replace the igniter if the ceramic is cracked or damaged.
Applies to: ECO Tec Series 3 boilers; gas valve removal optional
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 150-151. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.