Viessmann · Boiler troubleshooting

Check neutralizing system flow with burner removed

Vitocrossal 200 CI2

What is going on

With the burner removed, pour water into the combustion chamber. Water must drain freely from the condensate drain pipe without backing up.

Likely causes

  • Blocked condensate drain pipe

Check in this order

  1. Remove the burner.
  2. Pour water into the combustion chamber.
  3. Confirm water flows freely from the condensate drain pipe without backing up.
  4. If water backs up, clean the condensate drain pipe and repeat the check.

Applies to: Vitocrossal 200 CI2 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Service Instructions, p. 33. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.