Weil-McLain · Boiler troubleshooting
Check relief valve and expansion tank
What is going on
Relief valve and expansion tank checks for a relief valve that weeps.
Likely causes
- Waterlogged or undersized expansion tank
- Defective relief valve
- Over-pressurization of the system
Check in this order
- Lift the relief valve lever at least once a year to confirm water flows, with a discharge line piped to a safe place.
- If no water flows, shut the boiler down and replace the relief valve.
- If the valve weeps or will not seat, replace it, then confirm over-pressurization is not the cause.
- Closed-type tank check the tank fitting and fill level; replace with a larger tank if needed.
- Diaphragm or bladder tank confirm tank size is adequate; check charge pressure (usually 12 psig residential); replace the tank if it will not hold pressure.
- Have the relief valve reinspected at least every three years by a licensed plumbing contractor or authorized inspection agency.
Applies to: SVF 1500-3000
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 94-95. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.