Weil-McLain · Boiler troubleshooting

Zoning: three space heating zones with circulators (no DHW)

SlimFit Series 3

What is going on

Three thermostat zones each with its own circulator, all on PRIORITY 2.

Check in this order

  1. Check the 120 VAC outputs (page 60) and 24 VAC inputs (page 52) in the wiring section.
  2. Connect thermostats to P11-4/5, P15-1/2 and P15-3/4.
  3. Connect circulators to the P2 outputs.
  4. Confirm inputs 1, 2 and 3 are assigned to PRIORITY 2 (factory default).
  5. In the Wizard or the PRIORITY 2 menu, select the heating system type that matches the installed system.

Applies to: SlimFit Series 3 550/750 single boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.