Weil-McLain · Boiler troubleshooting
Power polarity fault on control
What is going on
The control is polarity-sensitive to incoming 120 VAC. With reversed polarity the control shows FAULT L1 POLARITY and will not cycle the boiler.
Likely causes
- Hot and neutral reversed on the 120 VAC supply
Check in this order
- Turn off power at the service entrance.
- Check the 120 VAC supply hot and neutral connections at the boiler junction box.
- Correct the polarity so the hot and neutral are wired properly.
- Restore power and confirm the FAULT L1 POLARITY message clears and the boiler cycles.
Applies to: CGi Series 5 spark-ignited pilot boilers (CGi-25, -3, -5, -6)
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 gas-fired water boiler manual, p. 46. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.