Viessmann · Boiler troubleshooting

Room air dependent combustion air supply

Vitocrossal 300 CA3B Dual Fuel

What is going on

Provide enough fresh combustion and ventilation air in the mechanical room. The room should never be under negative pressure. Exhaust, attic or dryer fans can pull air out faster than it can enter, so corrective air supply may be needed. Do not cover the boiler or store debris near it.

Likely causes

  • Exhaust, attic or dryer fans creating negative pressure
  • Louvers or openings blocked or undersized

Check in this order

  1. Locate the boiler near an outside wall where fresh air can be ducted directly.
  2. Size ducts using national codes. Round ducts are allowed.
  3. Check the free area of closet louvers. If unknown, assume 20 percent for wood louvers and 60 to 75 percent for metal louvers.
  4. Enlarge the opening to make up for louver blockage. Example: a 14 x 6 in free opening needs a 14 x 10 in opening with metal louvers.
  5. Test for negative pressure with fans running and add make-up air if needed.

Applies to: Room air dependent venting

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 54. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.