Blue banner or wrench symbol on the display
What is going on
The maintenance timer ran out (12 months by default). It only shows in standby and the boiler keeps running normally. A blue banner during a heating call is normal and is not this reminder.
Likely causes
- Scheduled maintenance date has passed
Check in this order
- Do the scheduled service.
- Contractor menu > Service Info > Reset Reminder updates the last and next maintenance dates.
- If the homeowner resets it, only the next date moves.
- Set Interval Settings to fit the service history, and enter your name and phone so they show on the reminder and on lockouts.
Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Control action - Standby/Maintenance, p.3; Homeowner menus p.56; Service menus p.72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.