Viessmann · Boiler troubleshooting
Heating system fill water and antifreeze
What is going on
Treat boiler water where minerals or hardness are high. The boiler suits only closed hot water systems with pumps. Antifreeze is allowed up to a 50/50 mix, and 40% gives freeze protection to -10°F (-23°C). Use only antifreeze made for hydronic heating; never automotive glycol. Antifreeze can require a backflow preventer on the feed and can affect expansion tanks and radiation, so check the system often.
Check in this order
- Flush the existing heating system before connecting the new boiler to remove dirt and sludge.
- Fill the boiler with suitable water only and bleed all air.
- Keep the cold water fill pressure at 18-20 psig maximum and equal to the expansion tank pressure.
- Check all connections, including those under insulation, for leaks before fitting insulation.
- Install boiler isolation valves and drain valves above them on the supply and return.
- If the boiler heats an indirect DHW tank, fit flow check valves on the pump discharge of loops without a mixing valve.
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 44. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.