Weil-McLain · Boiler troubleshooting
Clean heat exchanger pins with cleaning tool and water
What is going on
Loosen deposits between the heat exchanger pins, then flush them down to the base and out through the condensate line.
Check in this order
- Use the Heat Exchanger Cleaning Tool supplied with the boiler, or a piece of 20-gauge or lighter sheet metal about ¾ inch wide and 18 inches long.
- Slide the tool through the pins in the three directions shown in the cleaning figure.
- Vacuum most of the debris out of the base through the flue inspection opening.
- Disconnect the condensate line at the bottom of the heat exchanger and place a pan under the trap connection.
- Spray water through the burner opening onto the pins until debris is flushed into the base.
- Spray water into the flue inspection opening to flush the remaining sediment to the condensate outlet.
- Spray water through the condensate line to clean it, remove the pan, then reinstall the condensate line and the flue inspection plug.
Applies to: SlimFit SF-550 and SF-750 Series 3
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 106. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.