Rinnai · Boiler troubleshooting

Condensate drain line installation

I-Series Plus

What is going on

The boiler has an integrated condensate trap and the drain must be installed to prevent damage and freezing.

Check in this order

  1. Use only corrosion-resistant drain materials such as PVC pipe or plastic hose.
  2. Keep the drain pipe at least the same diameter as the 1/2 in MNPT drain connection along its whole length.
  3. Slope the drain toward the floor drain or condensate pump. Keep the pipe as short as possible with a downward pitch.
  4. Leave the drain end open to the atmosphere, not under water or other substances.
  5. Wrap drain lines in freezing areas with an approved heat source, installed per its maker's instructions.
  6. For outdoor installations, run the drain through an interior wall or between insulation and an interior wall to reduce freezing.
  7. Install a condensate pump if no floor drain is available or the drain is above the condensate drain outlet.
  8. Dispose of condensate according to local codes. Use a neutralizer kit where local code requires it.
  9. Do not install an external condensate trap, because the boiler has one built in.
  10. Do not connect the condensate drain to an air conditioning evaporator coil drain.

Applies to: Condensate drain piping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.