Viessmann · Boiler troubleshooting

Cast iron section assembly

Vitorond 200 VD2A

What is going on

Field assembly of a boiler shipped in separate sections. Only needed when the boiler arrives in individual sections. Hardware is in the accessory pack inside the combustion chamber and the Installation Fittings carton.

Check in this order

  1. Remove the boiler door, the installation accessories, the turbulator inserts (VD2A-125 to 195), the distribution tube and the tie rods. Keep all hardware.
  2. Remove the rear section and its studs from the return port, then set the rear section on the base with legs in the base channel and secure it against tipping.
  3. Clean all push nipples and nipple ports with solvent. Check ports for burrs and file only in a circular motion.
  4. Coat one half of each push nipple with linseed oil and graphite sealant, insert it, and tap it in evenly with a wood or rubber mallet. Coat the second half.
  5. Lay each intermediate section flat, gasket side up. Apply the supplied silicone into the grooves. Arrows point up when flat and toward the rear when installed.
  6. Align each section with the push nipples and seat them evenly with a pry bar.
  7. Insert the draw tool rods, lock the pressure flanges with wedges, align the nuts, then tighten evenly with the ratchet until the nipple ports touch. Do not over-force.
  8. Add only one section at a time during compression to prevent joint leaks.
  9. Join the front section, then fit tie rods with washers top and bottom. Hand tighten the nuts only.
  10. Remove the draw tool, install the distribution tube with gasket and cover, and fit the 2 in. bottom plug with approved sealant.

Applies to: VD2A-125 to VD2A-270 shipped in sections

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200, VD2A Series Installation, pp. 16-20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.