Viessmann · Boiler troubleshooting

Vent termination location requirements - Canada

Vitocrossal 200 CI2

What is going on

Vent must follow local rules plus CAN/CSA-B149.1 or .2. Flexible vent is only for vertical runs. Key limits: not less than 7 ft (2.13 m) above a paved walk or driveway on public property; not less than 6 ft (1.83 m) from a mechanical air inlet; not less than 1 ft (0.3 m) above grade or snow level; 1 ft (0.3 m) from a window or door that opens for inputs up to 100,000 Btu/h, and 3 ft (0.9 m) above 100,000 Btu/h; 3 ft (0.9 m) from a gas regulator vent or meter/regulator assembly; not under a veranda, porch, or deck unless open on two sides and more than 1 ft (0.3 m) below it; 3 ft (0.9 m) from an inside corner of outside walls.

Check in this order

  1. Confirm the vent does not end where the clearances above are not met.
  2. Keep the termination away from planters, patios, and windows where flue gas causes fogging.
  3. Keep the termination where flue gas will not hit brick, siding, or other construction, or hot gas will not cause damage or injury.
  4. Keep the termination 3 ft (0.9 m) from the property line where possible.

Applies to: Vent termination, Canada

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Installation Instructions, p. 51. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.