Weil-McLain · Boiler troubleshooting
Annual startup: inspect ignition electrode
What is going on
The ignition electrode is the longer rod with a brown ceramic insulator. It mounts on the burner end section.
Likely causes
- White oxide buildup on the electrode
- Worn or damaged gasket
- Ground wire loose
Check in this order
- Remove the ignition electrode from the burner end section of the heat exchanger.
- Remove white oxides with steel wool. If it cannot be cleaned well, replace the ignitor.
- Reinstall the electrode with the gasket in good condition and correctly positioned. Replace the gasket if needed.
- Make sure the ignitor ground wire is under the top screw that holds the ignitor to the casting.
- Ignition electrode must be on the burner end. Flame sensor must be on the piping end. Wrong placement can cause poor ignition and lockout.
Applies to: SlimFit 1000-2000 MBH Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 89. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.