Boiler water temperature too high or too low

Vitotronic 200

What is going on

Check whether the setpoint is wrong or whether the temperature measurement is at fault.

Likely causes

  • Wrong timer, heating curve or coding address settings
  • Faulty setpoint selector or remote control
  • Fault in the remote control connecting cable
  • Faulty boiler temperature sensor
  • Electro-mechanical adjustable high limit set incorrectly

Check in this order

  1. Compare the current boiler water temperature with the desired value.
  2. If the desired value is wrong check timer, heating curves and coding addresses.
  3. Check the setpoint selector and remote control (if fitted). Set a very high day temperature and a very low night temperature, and set the time so the operation changes from normal room temperature to reduced room temperature in a few minutes.
  4. Confirm the switchover causes a clear change in boiler water setpoint. If not, connect the remote control with its fixture directly to the Vitotronic and repeat the test.
  5. If the setpoint is now correct, the fault is in the remote control connecting cable.
  6. If the setpoint is still wrong, recheck the equipment settings and remote control and replace the remote control if needed.
  7. If the desired value is correct measure the boiler water temperature with a thermometer in the sensor well and compare it with the sensor resistance curve.
  8. Check the cut-off point of the electro-mechanical adjustable high limit.

Applies to: Vitotronic 200 KW2 boiler water temperature control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 200 service instructions, p. 42. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.