Viessmann · Boiler troubleshooting

Calibrate the burner and perform combustion analysis

Vitorond 100

What is going on

Verify factory settings and adjust for local conditions using calibrated equipment.

Likely causes

  • Weather, vent length and chimney size, side wall venting, altitude, oil quality and other fuel-burning appliances can all change results.

Check in this order

  1. Use calibrated combustion equipment at the final installation site.
  2. Measure CO2, stack temperature, draft and CO in the flue pipe between the boiler and the barometric draft regulator, before dilution air.
  3. Measure over-fire draft at the observation port (0 to +0.01 in. w.c.).
  4. Confirm breech draft is about -0.02 in. w.c. and not more than -0.08 in. w.c. without a barometric draft regulator.
  5. Adjust the burner until results are acceptable for local conditions. Check CO2 is within 11.0% to 13.5% for #2 oil.
  6. For burner technical data, see the table on p. 38 or p. 39. Refer to the burner manual and, for direct vent, the Direct Vent System Installation Instructions.

Applies to: Vitorond 100 VR1 with oil burner

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 100, VR1 installation and service instructions, p. 47. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.