Calibrate the burner and perform combustion analysis
What is going on
Verify factory settings and adjust for local conditions using calibrated equipment.
Likely causes
- Weather, vent length and chimney size, side wall venting, altitude, oil quality and other fuel-burning appliances can all change results.
Check in this order
- Use calibrated combustion equipment at the final installation site.
- Measure CO2, stack temperature, draft and CO in the flue pipe between the boiler and the barometric draft regulator, before dilution air.
- Measure over-fire draft at the observation port (0 to +0.01 in. w.c.).
- Confirm breech draft is about -0.02 in. w.c. and not more than -0.08 in. w.c. without a barometric draft regulator.
- Adjust the burner until results are acceptable for local conditions. Check CO2 is within 11.0% to 13.5% for #2 oil.
- For burner technical data, see the table on p. 38 or p. 39. Refer to the burner manual and, for direct vent, the Direct Vent System Installation Instructions.
Applies to: Vitorond 100 VR1 with oil burner
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100, VR1 installation and service instructions, p. 47. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.