Viessmann · Boiler troubleshooting

Connecting the flue gas pipe

Vitocrossal 300 CA3B Dual Fuel

What is going on

The flue collector is not designed to carry the weight of the vent system. Connections must be free of load and torque.

Check in this order

  1. Fully insert the flue gas adapter into the flue outlet if stainless steel piping is used.
  2. Fully seat the venting system in the flue gas collector.
  3. Keep the run to the flue as short as possible with a slight rise of at least 2° to 3°. Avoid sharp bends.
  4. Support all vent components with an anchor system that meets the vent manufacturer's instructions.
  5. Check all vent and coupling connections for leaks with a certified leak detector.
  6. Use a flue adapter from the vent manufacturer if the collector outlet does not match their system.

Applies to: Flue gas vent connection

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 installation instructions, p. 38. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.