Viessmann · Boiler troubleshooting
Wiring the Vitodens 100-W WB1A/WB1B boiler to the Versatronik 10.WB1
What is going on
Interconnect the boiler pump module with the Versatronik for the low voltage DHW and room thermostat signals and for the 120VAC pump supply and pump signal. Power is applied only after all connections are checked.
Check in this order
- Disconnect the boiler and the Versatronik from 120VAC before starting any work.
- Wire X4.1 and X4.2 from the Vitodens pump module to the WB1 DHW terminals (X7.1 and X7.2) on the Versatronik.
- Wire X4.3 and X4.4 from the Vitodens pump module to the WB1 RT terminals (X8.3 and X8.4) on the Versatronik.
- Wire the N and L boiler pump output from the Vitodens pump module to the WB1 pump N and L input on the Versatronik PCB.
- Connect the room thermostat as a potential-free contact only, with no voltage applied. Do not use it with the Versatronik Como OT.
- Connect the DHW call as a potential-free contact from a set-point control or DHW tank aquastat, with no voltage applied.
- Connect the DHW pump (120VAC, 3 FLA output) and the space heating pump (120VAC, 3 FLA output).
- Check all connections before applying 120VAC to the Versatronik.
Applies to: Vitodens 100-W WB1A and WB1B with Versatronik 10.WB1
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 10.WB1 installation manual, p. 10-11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.