Weil-McLain · Boiler troubleshooting
No space heating in mild weather, display shows WWSD
What is going on
Warm weather shutdown blocks space heating when the outdoor temperature is above the WWSD setting. The boiler sits in standby and the display shows WWSD. DHW and Custom priorities are not blocked.
Likely causes
- Outdoor temperature is above the WWSD setting
- Outdoor sensor reading is off
Check in this order
- Compare the outdoor temperature on the boiler information screen with WWSD Temp in Boiler Settings.
- Lower WWSD or set it to OFF if the customer needs heat at that temperature.
- WWSD needs the outdoor sensor. Without a sensor, WWSD must be OFF.
- If the outdoor reading looks wrong, use Adjust Outdoor in Boiler Settings to calibrate it.
- Check the sensor mounting outside wall, out of direct sun and away from other heat or cooling, wire outlet pointing down.
Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Control action - WWSD, p.3; Boiler Settings, p.58; Field wiring E, p.13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.