Descale the plate heat exchanger with vinegar and rinse
What is going on
Vinegar flush for lime scale on the plate heat exchanger, followed by a rinse. Use undiluted food-grade white vinegar, about four gallons. Flush the boiler at least 1 hour at about four gallons per minute. Water treatment is recommended to prevent scale.
Check in this order
- Shut off the gas supply to the boiler.
- Turn off the DHW and CH buttons on the controller.
- Close the shutoff valves on the hot and cold water lines (V3 and V4).
- Connect the pump outlet hose (H1) to the cold water line at service valve V2.
- Connect the drain hose (H3) to the hot water line at service valve V1.
- Pour about four gallons of undiluted food-grade white vinegar into a pail.
- Place the drain hose (H3) and the pump inlet hose (H2) into the cleaning solution.
- Open service valves V1 and V2.
- Remove the front panel by taking out its two screws.
- Press the SW3 button on the PC board (lower left of the unit) to enter descaling mode.
- Use the up or down arrow to select dES, then press Select.
- Run the pump so the vinegar circulates for at least 1 hour at about 15.1 L/min.
- Press the DHW button to start the 60-minute countdown and watch for the time to count down.
- After the countdown, the display shows rnS. Stop the pump when done.
- Turn the pump off.
- Drain the vinegar remove hose H3 from the pail and place it in a sink or outside. Close V2 and open V4 only, letting water flow for five minutes.
- Close V4 when draining is finished. Remove the in-line filter at the cold water inlet, clean out residue, refit it, and open V4.
- Close V1 and open V3.
- Press Select until End shows.
- Disconnect all hoses.
- Press Select to go back to dES, then press SW3 on the PC board to return to normal mode.
- Refit the front panel and restore the gas supply.
Applies to: I-Series Plus condensing combi boiler
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, pp. 128-130. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.