External heating program changeover (EA1 extension)
What is going on
A potential-free contact can switch the operating program for heating circuits 1 to 3. Each circuit can be changed over separately.
Check in this order
- Set 5D (DE1), 5E (DE2) or 5F (DE3) in the General group to 1.
- Assign the function to each heating circuit at coding d8 in the Heating circuit group.
- Use a potential-free contact only.
Applies to: Heating circuits 1 to 3
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 installation instructions, p. 34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.