Pump (circulator) zoning with primary/secondary piping
What is going on
Each zone gets its own circulator. The boiler circulator cannot be used as a zone pump.
Likely causes
- Boiler circulator wired as a zone pump
- More than three zones without a zone controller
Check in this order
- Install a separate circulator for each zone, sized for the required flow and head.
- Install a flow/check valve on the boiler outlet piping.
- Use at least the minimum pipe size from Figure 12 (page 15) on all boiler loop piping.
- Do not use the boiler circulator for a zone pump.
- For more than 3 zones, add a Weil-McLain WMCR zone circulator controller.
- If DHW is a zone, use the Advanced Manual to set the boiler circulator to run during DHW demand and set TARGET MOD SENSOR to System Supply.
Applies to: SlimFit 1000-2000 Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 Boiler Manual, p. 19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.