Pump (circulator) zoning with primary/secondary piping

SlimFit Series 2

What is going on

Each zone gets its own circulator. The boiler circulator cannot be used as a zone pump.

Likely causes

  • Boiler circulator wired as a zone pump
  • More than three zones without a zone controller

Check in this order

  1. Install a separate circulator for each zone, sized for the required flow and head.
  2. Install a flow/check valve on the boiler outlet piping.
  3. Use at least the minimum pipe size from Figure 12 (page 15) on all boiler loop piping.
  4. Do not use the boiler circulator for a zone pump.
  5. For more than 3 zones, add a Weil-McLain WMCR zone circulator controller.
  6. If DHW is a zone, use the Advanced Manual to set the boiler circulator to run during DHW demand and set TARGET MOD SENSOR to System Supply.

Applies to: SlimFit 1000-2000 Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.