Inspect and clean the condensate trap
What is going on
Clean the trap if debris has built up and confirm the drain flows freely.
Likely causes
- Debris accumulated in the trap
- Obstructed condensate drain line
Check in this order
- Inspect the condensate trap; if debris has built up, remove the trap and clean it (see p. 61 for removal and reinstallation)
- Loosen the hose clamps at the trap inlet and outlet, remove the trap and flush it as needed
- Check the trap for cracks or damage and confirm the inlet and outlet connections are in good condition
- Reinstall the trap
- Fill the trap with fresh water by pouring into the flue adapter test port; keep filling slowly until water flows out of the condensate drain line
- Confirm the trap line is unobstructed and drains freely (see p. 95)
- Verify all connections are leak-free
Applies to: SVF 500/600 Series 1 boiler
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 boiler manual, p. 105. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.