Weil-McLain · Boiler troubleshooting

Inspect and clean the condensate trap

SVF 500/600 Series 1

What is going on

Clean the trap if debris has built up and confirm the drain flows freely.

Likely causes

  • Debris accumulated in the trap
  • Obstructed condensate drain line

Check in this order

  1. Inspect the condensate trap; if debris has built up, remove the trap and clean it (see p. 61 for removal and reinstallation)
  2. Loosen the hose clamps at the trap inlet and outlet, remove the trap and flush it as needed
  3. Check the trap for cracks or damage and confirm the inlet and outlet connections are in good condition
  4. Reinstall the trap
  5. Fill the trap with fresh water by pouring into the flue adapter test port; keep filling slowly until water flows out of the condensate drain line
  6. Confirm the trap line is unobstructed and drains freely (see p. 95)
  7. Verify all connections are leak-free

Applies to: SVF 500/600 Series 1 boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 105. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.