Weil-McLain · Boiler troubleshooting

Zoning two space heating zones with zone valves

Evergreen ProSeries 2

What is going on

Layout for two space heating zones using zone valves (120VAC or 24VAC) with a system circulator and no indirect DHW.

Check in this order

  1. Review the 120VAC output and 24VAC input wiring pages (49 and 50).
  2. Wire space heating thermostats to INPUT 2, 3 and 4. INPUT 1 is reserved for the system circulator.
  3. Set System Settings 2, 3 and 4 to PRIORITY 2 and choose the space heating system type that matches the system.
  4. Keep the factory default settings for the heating system type, or change them if needed.
  5. Assign INPUT 1 to AUX PUMP/OUTPUT, then select INPUTS PRIORITY SETTING when prompted for when to activate the output.
  6. Confirm that Priority 2 RUN AUX PUMP/OUT is set to YES so the system pump runs when either zone calls for heat.
  7. Do not use J17-1/2 for a wired connection, because it drives the system circulator.
  8. Install a by-pass pressure regulating valve, because flow can occur with the zone valves closed.

Applies to: Evergreen Pro control, two-zone space heating with zone valves and a system circulator

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.