Zoning two space heating zones with zone valves
What is going on
Layout for two space heating zones using zone valves (120VAC or 24VAC) with a system circulator and no indirect DHW.
Check in this order
- Review the 120VAC output and 24VAC input wiring pages (49 and 50).
- Wire space heating thermostats to INPUT 2, 3 and 4. INPUT 1 is reserved for the system circulator.
- Set System Settings 2, 3 and 4 to PRIORITY 2 and choose the space heating system type that matches the system.
- Keep the factory default settings for the heating system type, or change them if needed.
- Assign INPUT 1 to AUX PUMP/OUTPUT, then select INPUTS PRIORITY SETTING when prompted for when to activate the output.
- Confirm that Priority 2 RUN AUX PUMP/OUT is set to YES so the system pump runs when either zone calls for heat.
- Do not use J17-1/2 for a wired connection, because it drives the system circulator.
- Install a by-pass pressure regulating valve, because flow can occur with the zone valves closed.
Applies to: Evergreen Pro control, two-zone space heating with zone valves and a system circulator
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 61. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.