Weil-McLain · Boiler troubleshooting

Wire external limit with automatic reset

ECO Tec Series 3

What is going on

Boiler shuts down when the limit opens and restarts automatically after the limit closes.

Check in this order

  1. Remove the factory-installed jumper on J20 pins 3 and 4.
  2. Connect the isolated contacts of the external limits across J20 pins 3 and 4.
  3. When the limit opens, the boiler shuts down.
  4. The boiler restarts automatically 150 seconds after the limit closes.

Applies to: ECO Tec Series 3 all models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 71. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.