Viessmann · Boiler troubleshooting
Connecting two remote control units
What is going on
Up to 2 remote controls can connect to one boiler control unit, and this can be one Vitotrol 200A with one Vitotrol 300A. Connect them through a field-supplied junction box. The total KM BUS cable length for all participants must not exceed 164 ft (50 m). The manual shows two wiring versions; the second version adds other KM BUS users through the same junction box. For the Vitotrol 300A wiring, use its own installation instructions.
Check in this order
- Check that only one Vitotrol 200A and one Vitotrol 300A, or two of the same type, are on the control unit.
- Wire all remotes and any other KM BUS users through a field-supplied junction box, following the diagram.
- Keep the total KM BUS cable length at or below 164 ft (50 m).
- Refer to the Vitotrol 300A installation instructions for its connection details.
Applies to: Vitotrol 200A with Vitotrol 300A or other KM BUS users
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotrol 200A installation, operating and service instructions, p. 6. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.