Common vent spillage test when a boiler is removed

I-Series Plus

What is going on

Required by ANSI Z21.13 when an existing boiler is taken off a common vent. The remaining appliances on the vent must be checked to confirm they still vent safely.

Likely causes

  • Common vent may be oversized for the remaining appliances once the boiler is removed

Check in this order

  1. Seal any unused openings in the common vent system.
  2. Inspect the vent for correct size, horizontal pitch, blockage, leakage and corrosion.
  3. Close building doors, windows and doors to other spaces. Run clothes dryers and non-vented appliances, and run exhaust fans such as range hoods and bathroom fans at full speed. Do not run a summer exhaust fan. Close fireplace dampers.
  4. Light the appliance under test and run it continuously.
  5. After five minutes of main burner operation, check for spillage at the draft hood relief opening with a match, candle or smoke.
  6. After testing, restore doors, windows, fans, dampers and other gas appliances to their previous state.
  7. Correct any improper venting so it meets NFPA 54 / ANSI Z223.1 or CAN/CSA B149.1, resizing toward the minimum size from the code tables.

Applies to: Boilers on common vent systems

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 140. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.