Rinnai · Boiler troubleshooting
Common vent spillage test when a boiler is removed
What is going on
Required by ANSI Z21.13 when an existing boiler is taken off a common vent. The remaining appliances on the vent must be checked to confirm they still vent safely.
Likely causes
- Common vent may be oversized for the remaining appliances once the boiler is removed
Check in this order
- Seal any unused openings in the common vent system.
- Inspect the vent for correct size, horizontal pitch, blockage, leakage and corrosion.
- Close building doors, windows and doors to other spaces. Run clothes dryers and non-vented appliances, and run exhaust fans such as range hoods and bathroom fans at full speed. Do not run a summer exhaust fan. Close fireplace dampers.
- Light the appliance under test and run it continuously.
- After five minutes of main burner operation, check for spillage at the draft hood relief opening with a match, candle or smoke.
- After testing, restore doors, windows, fans, dampers and other gas appliances to their previous state.
- Correct any improper venting so it meets NFPA 54 / ANSI Z223.1 or CAN/CSA B149.1, resizing toward the minimum size from the code tables.
Applies to: Boilers on common vent systems
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 140. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.