Weil-McLain · Boiler troubleshooting

Condensate drain check (220/299/300/399)

Evergreen Series 2

What is going on

On larger models, flue gas smell or escaping flue gas at the condensate drain or tee means the trap is dry. The drain line must also run freely.

Likely causes

  • Dry condensate trap
  • Obstructed condensate drain line

Check in this order

  1. With the boiler running, hold fingers in front of the discharge end of the condensate tubing and the open top of the condensate tee. Check for flue gas.
  2. If flue gas escapes, the trap is dry. Fill it using the test port procedure.
  3. Slowly pour water into the top of the PVC tee on the side of the boiler. Water should run out the end of the condensate drain line.
  4. If water does not run out, call a service technician to clean or replace the drain line.
  5. If the trap runs dry regularly, call a service technician to inspect the boiler and condensate line.

Applies to: 220/299/300/399 Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Evergreen Series 2 user's information manual, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.