Weil-McLain · Boiler troubleshooting

Nothing on display and no other components running (no 120 V)

SlimFit Series 2

What is going on

Control is not receiving 120 V power.

Likely causes

  • Service switch or breaker off
  • Power supply problem to service switch
  • Wiring fault inside control pod
  • Blown 12-amp fuse

Check in this order

  1. Check the service switch and/or circuit breaker is on.
  2. Check for 120 VAC at the service switch; troubleshoot the supply if absent.
  3. Check for 120 VAC at the line voltage terminal block in the top left electrical compartment.
  4. Correct wiring inside the control pod per the wiring diagram.
  5. Inspect the 12-amp fuse (see page 94) and replace with the proper part if needed.

Applies to: SlimFit 1000-2000 Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SlimFit Series 2 boiler manual, p. 97. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.